Sign In | Join Free | My qualitytoyschina.com |
|
Certification : ISO9001
MOQ : 30
Price : 1
Model NO. : YH5CX-12
Installation Type : Fixed
Material : ZnO
Discharge Current : 5ka
Voltage : 12kv
Flow Capacity : 100kA
CTI Level : 6
Nominal System Voltage : 10
Rated Voltage : 17
Minimum Reference Voltage : 20
Power Frequency Withstand : 26
High Current Impulse : 65/80
SW Through-flow Capacity : 150/250
Creepage Distance : IV level heavy pollution
Shape : Cuboid
Type | Nominal System Voltage | Rated Voltage | Minmum Reference Voltage under 1 mA DC | MRV under 1/5 μ s Steep Discharge Current | MRV under 8/20 μ s Lightning Discharge Current | MRV under 1.2/50μ S Impulse Discharge Voltage | Power Frequency Withstand Voltage | 4/10 μ s High Current Impulse Twice (KA) | 2mS SW through-flow capacity A/18 | |||
5kA | 5kA | |||||||||||
YH5CX-13/40 | 10 | 17 | 20 | 46 | 40 | 100 | 26 | 65/80 | 150/250 | |||
YH5CX5-17/50 | 10 | 17 | 25 | 57.5 | 50 | 100 | 28 | 85/100 | 250/400 | |||
YH5CX5-26/65 | 20 | 26 | 37 | 75 | 65 | 160 | 60 | 85/100 | 250/400 | |||
YH5CX-29/73 | 20 | 29 | 41 | 75 | 65 | 160 | 65 | 85/100 | 250/400 |
![]() |
YH5CX-12 12kV C-Type Gap Metal Oxide Arrester for AC/DC Systems Images |